Minus sign display for the monitors (Pr.290)
• A negative output can be selected for the monitor display of the terminal AM (analog voltage output), the operation panel,
and a communication option. For a list of the monitors that can output values with minus signs, refer to the monitor
description list (on
page
348).
• Negative output is available for FR Configurator2 or the trace function.
Pr.290 setting
Terminal AM
0 (initial value)
1
Enabled
2
3
Enabled
4
5
Enabled
6
7
Enabled
—: Disabled (unsigned numbers only)

The following communication does not support the negative output.
RS-485 communication (Mitsubishi inverter protocol, MODBUS RTU), SLMP communication, and HMS network option

Under the condition that the high-speed sampling and the negative output are selected for FR Configurator2, the display range of the output
frequency (Monitor No.1) is -300.00 Hz to 300.00 Hz. A value outside the range is clamped at -300.00 Hz or 300.00 Hz. Under the same
condition, the display range of the running speed (Monitor No.6) is -30000 r/min to 30000 r/min. A value outside the range is clamped at -30000
r/min or 30000 r/min. During the trace sampling, the same display ranges are applied. A value outside the ranges is clamped.
• Select items to be displayed with minus signs using Pr.1018 Monitor with sign selection.
Monitor item
Output frequency
Motor speed
Motor torque
Position command (lower)

Position command (upper)

Current position (lower)

Current position (upper)

Droop pulse (lower)

Droop pulse (upper)

Torque command
Torque current command
Torque monitor (power driving / regenerative driving
polarity switching)
Motor temperature
PID deviation
Cumulative pulse
Cumulative pulse overflow times
Cumulative pulse (control terminal option)
Cumulative pulse overflow times (control terminal option)
Remote output 1
Remote output 2
Remote output 3
Remote output 4
PID manipulated amount
Second PID deviation
Second PID manipulated amount
Control circuit temperature
○: Displayed with minus signs, —: Displayed without minus signs (unsigned numbers only)

Displayed without minus signs on the operation panel. Confirm the rotation direction with the [FWD] or [REV] indicator.

Signed values are displayed only on the FR-DU08 (-9999 to 9999). Unsigned values (0 to 9999) are displayed on other devices.

Full 32-bit data (-2147483648 to 2147483647) is displayed during monitoring via the communication option.

Monitor the lower and upper digits at the same timing. Otherwise, the data may not be reliable.
(M) Monitor display and monitor output signal
Connection port
Operation panel
Communication option
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
9999






FR Configurator2 etc.

Enabled
Enabled
Enabled
Enabled
Pr.1018 setting
0
1
















PARAMETERS

5
GROUP
M
355