How Should I Set And Add The Smoke Sensor (Connected To The Ai/Di Port On The Uim20A Expansion Module) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Table 8-22 Function check
Check Method
Simulate a smoky
environment under
the smoke sensor.
----End
8.1.6.24 How Should I Set and Add the Smoke Sensor (Connected to the
AI/DI Port on the UIM20A expansion module)?
If a smoke sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the network cable has been stripped, core wires 1, 5, and 8 have been
short-circuited, core wires 6 and 7 have been connected to the cable delivered with the smoke
sensor, and the other end of the network cable has been connected to the AI/DI port on the
UIM20A expansion module.
Context
Procedure
Step 1 Set smoke sensor parameters.
1.
2.
3.
4.
Step 2 Check the monitoring functions of smoke sensor.
Table 8-23 Function check
Check Method
Simulate a smoky
environment under
the smoke sensor.
----End
Issue 06 (2020-04-22)
Normal Connection Status
Smoke sensor status(AI/DI_1)
is displayed on the active alarm
page of the app or WebUI.
If the sensor is prefabricated, only check its settings.
The actual value prevails. Only the method of the parameter settings is described.
In this example, the smoke sensor is connected to the AI/DI_1 port on the UIM20A expansion module.
Log in to the ECC800-Pro WebUI as an administrator.
Choose Monitoring > System > UIM Group> UIM n > Running Parameters.
In AI/DI_1 Port Settings area, set AI/DI_1 sensor to Enable, click Submit.
Set AI/DI_1 sensor type to Smoke sensor, click Submit.
Normal Connection Status
Smoke sensor status(AI/DI_1)
is displayed on the active alarm
page of the app or WebUI.
Copyright © Huawei Technologies Co., Ltd.
Alarm Clearance Method
If Smoke sensor type is Smoke
Sensor, power off and reset the
smoke sensor to clear the alarm.
Alarm Clearance Method
If Smoke sensor type is Smoke
Sensor, power off and reset the
smoke sensor to clear the alarm.
8 FAQ
256

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecc800-pro

Table of Contents