Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose System Settings > Linkage Control.
Step 3 Ensure that Enable linkage control function is Yes.
Step 4 On the Linkage Group tab page, set Intelligent lighting to on.
Step 5 Check and configure the wireless networking (802.15.4) function of the AC actuator.
Before networking, ensure that both the ECC800-Pro and AC actuator have no network
parameters. That is, the RF_Z indicators on the ECC800-Pro and AC actuator are both steady
green.
1.
2.
3.
4.
Step 6 Set running parameters for the AC actuator.
Issue 06 (2020-04-22)
If a foreign object is hung on the skylight ceiling of the smart module and when the foreign object
moves, the camera may mistakenly generate a motion detection alarm to change the lighting status.
When the human body moves, the camera generates a motion detection alarm and the lighting is
turned on. If the motion amplitude of the human body is small, the camera cannot generate the
motion detection alarm. If the lighting is turned off due to this reason, wave to the camera and the
lighting is turned on again.
If light greatly changes outside the smart module, the camera may mistakenly generate a motion
detection alarm and the lighting is mistakenly turned on.
If you manually turn off the lighting when you leave the smart module, the lighting may be turned
on again when the camera detects that the person leaves.
The effective detection distance of the multi-functional sensor is 2.5 m.
If the RF_Z indicator on the ECC800-Pro is not steady green, hold down the SW button
on the ECC800-Pro for 8 to 20 seconds to erase network parameters.
If the RF_Z indicator on the AC actuator is not steady green, hold down the BLINK
button on the AC actuator for more than 10 seconds to make the AC actuator enter
non-networking status.
Hold down the SW button on the ECC800-Pro main control module for 3–5 seconds.
The RF_Z indicator on the ECC800-Pro main control modules turns from steady green
to blinking green at super short intervals (blinking at 10 Hz, on for 0.05 seconds and then
off for 0.05 seconds). The ECC800-Pro enters the wireless networking (802.15.4) pairing
status.
Hold down the BLINK button on the AC actuator for 2 seconds (1–5 seconds allowed).
The RF_Z indicator on the AC actuator turns from steady green to blinking green
intermittently at super short intervals (blinking at super short intervals for 0.5 seconds
and then off for 0.5 seconds). The component enters the wireless network search status.
After the wireless networking (802.15.4) pairing succeeds, the RF_Z indicator on the AC
actuator starts to blink at long intervals.
After all AC actuators are networked, hold down the SW button on the ECC800-Pro
main control module for 3–5 seconds. The RF_Z indicator on the ECC800-Pro main
control modules turns from blinking green at super short intervals to blinking green at
long intervals (blinking at 0.5 Hz, on for 1 second and then off for 1 second). The
ECC800-Pro exits the wireless networking (802.15.4) pairing status.
If two or more ECC800-Pro controllers need to be networked in wireless (802.15.4) mode, only one
system can be networked at one time. During the networking, ensure that the RF_Z indicators on the
ECC800-Pro main control modules of other systems are blinking at long intervals or steady on.