Huawei ECC800 User Manual page 203

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
WebUI Operations
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 If the iCooling function needs to be used, choose Monitoring > Cooling > Running
Parameters. On the iCooling parameter setting page, set Enable iCooling to Yes and click
Submit to finish the iCooling function setting.
Figure 6-52 Setting the iCooling function
Step 3 Set the iCooling temperature set point and humidity setpoint according to the actual
environment.
Figure 6-53 Setting the temperature and humidity setpoints
Issue 06 (2020-04-22)
communication between the slave and master units as well as communication between
the master unit and the ECC800-Pro is normal.
The WebUI displays the Enable iCooling page only for smart cooling products that
support the iCooling function.
The scenario is dual-row cold aisle containment and the following conditions are met:
Smart cooling product should be placed face to face.
The smart module is configured with an integrated UPS or integrated PDU.
Electricity has been configured for IT cabinets, network cabinets, and smart cooling
products. The ECC800-Pro collects statistics on IT branch power information,
which is mapped to IT cabinets and network cabinets.
Rack environment units or UIM20A expansion module and cabinet-level
temperature sensors are installed for IT cabinets or network cabinets. The
ECC800-Pro can monitor the temperature of each cabinet.
At least one cold-aisle temperature and humidity sensor is installed for each smart
cooling product, and each smart cooling product can detect the sensor readings.
When iCooling is enabled, smart cooling products enter the iCooling teamwork control mode.
The temperature and humidity refer to the values at the air intake vents of the IT cabinets.
After iCooling linkage is enabled, if the preceding conditions are not met, the smart cooling product
automatically exits the iCooling teamwork mode and enters the standalone mode. To view Team
work status, choose Monitoring > Cooling > NetCol5000 > Running Info > Status Information.
When iCooling is enabled, the T/H threshold can only be set on the ECC800-Pro WebUI.
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
192

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecc800-pro