ECC800 Data Center Controller
User Manual (for ECC800-Pro)
cascading power port
(5) 48V_OUT1
power output port
(9) BLINK button
Specifications
Table 3-25 Technical specifications for a smart ETH gateway
Item
Power input
Power output
FE port
POE port
BLINK
button
Indicators
Table 3-26 Indicators on a smart ETH gateway
Indica
tor
PWR
RUN
Issue 06 (2020-04-22)
signal port
(6) 48V_OUT2
power output port
(10) Status indicator
Specifications
PWR_IN D-type power input terminal, for power cascading, input voltage
range: 45–55 V DC
Power of a single smart ETH gateway: max (2.7 A, 48 V DC); power of
cascaded smart ETH gateways: max (25 A, 48 V DC)
PWR_OUT D-type power output terminal, for power cascading, output
voltage range: 45–55 V DC
48V_OUT1 and 48V_OUT2, terminal (1 A, 48 V DC), output voltage
range: 45–55 V DC
Two FE ports, RJ45 terminal with an indicator, 10/100M communication
rate, for the cascading between smart ETH gateways and the
communication with the upper computer
Four POE ports, RJ45 terminal with an indicator, 10/100M
communications rate, complying with IEEE802.3, IEEE802.3u,
IEEE802.3af/at
If you press the BLINK button, the RUN indicator blinks intermittently at
super short intervals (blinking at super short intervals for 0.5s and then off
for 0.5s) for 5 seconds.
Color
Name
Green
Power input
status
indicator
Module
Green
running
status
indicator
Copyright © Huawei Technologies Co., Ltd.
ports
(7) FE_2
cascading signal
port
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
The power supply is
Off
abnormal.
Blinking at
The smart ETH gateway
long
successfully registers with the
3 Device Description
(8) PWR_OUT