ECC800 Data Center Controller
User Manual (for ECC800-Pro)
2.
3.
4.
5.
6.
7.
8.
Step 4 Check the door status sensor functions.
Table 6-11 Function check
Check Method
Open the cabinet door.
----End
6.4.2 Commissioning an Access Control Device and a Cabinet
Electronic Lock
If an access control device and cabinet electric lock are installed, perform the following steps
to configure it.
Prerequisites
Procedure
Step 1 Set the access user management and access permission management.
1.
2.
Issue 06 (2020-04-22)
Choose System Settings > Signal Name Modify. The Batch Signal Configuration
page is displayed.
Set Device Type to UIM, set Device Name to UIM, and click OK.
On the query result tab page, set the new signal name of AI/DI_1 to Door2 and click
Submit.
Order number of door sensor name is same as that of the cabinet.
Choose Monitoring > System > UIM Group > UIM1 > Running Parameters >
AI/DI_1 Port Settings.
Set Door2 sensor to Enable and click Submit.
Set Door2 sensor type to Door sensor, ensure that Door2 power supply is set to Yes,
and click Submit.
Perform the preceding operations to set parameters for ports AI/DI_2 to AI/DI_8.
A maximum of eight access actuators are supported.
When the fingerprint reader is connected to the ECC800-Pro for the first time, the
permissions need to be synchronized.
Choose System Settings > Access Management to access the access management page.
The system supports the management of various access permissions through the access
card, password, and fingerprint.
Click Authentication Mode and set the authorization mode for the access actuator.
Select Card, Fingerprint, Card and password, Card and fingerprint, Fingerprint
and password, Card, password and fingerprint or Card, password or fingerprint.
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
Door1 DI alarm is generated on the active alarm page
of the app or WebUI.