Procedure
Step 1 Set smoke sensor parameters.
1.
2.
3.
4.
Step 2 Check the monitoring functions of smoke sensor.
Table 8-29 Function check
Check Method
Simulate a
smoky
environment
under the smoke
sensor.
----End
8.1.7.32 How Can I Set and Add the Smoke Sensor (Connected to the AI/DI
Port on the UIM20A expansion module)?
If a smoke sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the network cable has been stripped, core wires 1, 5, and 8 have been
short-circuited, core wires 6 and 7 have been connected to the cable delivered
with the smoke sensor, and the other end of the network cable has been
connected to the AI/DI port on the UIM20A expansion module.
Context
Procedure
Step 1 Set smoke sensor parameters.
Issue 02 (2020-09-07)
NO TE
In this example, the smoke sensor is connected to the AI/DI_1 port on the rack environment
unit.
Log in to the ECC800-Pro WebUI as an administrator.
Choose Monitoring > Cabinet > IT Cabinet n > Cabinet Collector n >
Running Parameters.
In AI/DI_1 Port Settings area, set AI/DI_1 sensor to Enable, and click
Submit.
Set AI/DI_1 sensor type to Smoke sensor, and click Submit.
Normal Connection Status
Smoke sensor status(AI/
DI_1) is displayed on the
active alarm page of the app
or WebUI.
If the sensor is prefabricated, only check its settings.
The actual value prevails. Only the method of the parameter settings is
described.
Copyright © Huawei Technologies Co., Ltd.
Alarm Clearance Method
If Smoke sensor type is
Smoke Sensor, power off
and reset the smoke sensor
to clear the alarm.