ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Table 5-7 Access authorization
Access authorization
Access authorization fails and the aisle door
cannot be opened.
Access authorization succeeds and the door
can be opened.
----End
Follow-up Procedure
To modify the parameters of a single eLight, do as follows:
1.
2.
Table 5-8 Function check
Item
Associated alarm
severity
Issue 06 (2020-04-22)
Figure 5-9 eLight actuator position
The eLight actuator is automatically associated with the nearest access actuator in the smart module
view.
If there are one access actuator and two eLight actuators in an aisle, the access actuator is
automatically associated with the two eLight actuators.
Choose Monitoring > Aisle > eLight Actuator Group > eLight Actuator. The
Running Parameters page is displayed.
Select the Associated alarm severity as required and click Submit.
Alarm Severity
Selection
Critical
Critical, Major
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Description
Red light, blinking for 3 seconds
Green light, blinking for 3 seconds
Description
If there is a critical alarm, the eLight
strip light turns on with a red light.
If there are multiple alarms, the eLight
106