Huawei ECC800 User Manual page 142

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Table 6-16 Function commissioning
Check Method
Attempt to open the door by pressing the
skylight button when the aisle door is
closed.
Step 3 Check functions of the atmosphere light.
Table 6-17 Function commissioning
Check Method
Press the atmosphere light
button.
Step 4 Check functions of the emergency button.
Table 6-18 Function commissioning
Check Method
Attempt to open the door by
pressing the emergency button
when the aisle door is closed.
Step 5 Check functions of the magnetic lock.
Table 6-19 Function commissioning
Check Method
When the aisle door is
normally closed, check
whether there is a door open
alarm on the ECC800-Pro.
----End
Issue 06 (2020-04-22)
Normal Connection Status
The atmosphere light is steady blue.
Normal Connection
Status
The aisle door is
opened successfully.
Normal Connection
Status
There is no door open
alarm on the
ECC800-Pro.
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
The skylight can be opened manually.
Follow-up Procedure
You need to restore the
emergency button.
Troubleshooting
If a door open alarm is reported
when the door is closed,
relocate the magnetic lock and
magnet to minimize the
deviation until the door open
alarm is cleared.
6 Feature Description
131

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecc800-pro

Table of Contents