How To Set And Add The Wlds900 Water Sensor - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)

8.1.6.25 How to Set and Add the WLDS900 Water Sensor?

If a water sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the straight-through cable has been connected to the RJ45 port on the WLDS900
water sensor, and the other end has been connected to the AI/DI port on the ECC800-Pro.
Context
Procedure
Step 1 Set water sensor parameters.
1.
2.
3.
4.
5.
6.
7.
8.
Step 2 Check functions of water sensors.
Table 8-24 Function check
Check Method
Immerse the water detection
cable in water.
----End
Issue 06 (2020-04-22)
To use the AI/DI sensor, enable the corresponding AI/DI port and name the sensor. The
specific alarm then can be reported.
If the sensor is prefabricated, only check its settings.
The actual value prevails. Only the method of the parameter settings is described.
In this example, the water sensor is connected to the AI/DI_1 port on the ECC800-Pro.
The default alarm severity of the AI/DI port is Minor. If you want to change the alarm severity, see
How Should I Configure Alarm Parameters.
Log in to the ECC800-Pro WebUI as an administrator.
Choose System Settings > Signal Name Modify. The Batch Signal Configuration
page is displayed.
Set Device type to ECC800, set Device name to ECC800, and click OK.
On the query result tab page, set the new signal name of AI/DI_1 to Leak and click
Submit.
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_1 Port
Settings.
Set Leak sensor to Enable and click Submit.
Confirm that Leak sensor type is automatically identified as Leak sensor(Rope).
Click Unhide All Advanced Signals, then click Power Supply Parameters. Ensure that
III power supply enable(AIDI_1/DO) is Yes.
Copyright © Huawei Technologies Co., Ltd.
Normal Connection
Status
Leak DI alarm is generated
on the active alarm screen of
the app or on the WebUI.
Alarm Clearance Method
Wipe dry the water
detection cable. The alarm
disappears automatically.