Huawei ECC800 User Manual page 115

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
2.
Step 2 Set parameters for power distribution units on the ECC800-Pro WebUI.
1.
2.
3.
Table 5-4 Power distribution settings for a power distribution unit
Path
Monitoring >
Power
Distribution >
General Input
Unit1 > Power
Distribution
Unit > Running
Parameters >
Unhide All
Advanced
Signals >
Power
Distribution
Settings
4.
----End
Issue 06 (2020-04-22)
Set the parameters for other general input units in the same way or by synchronizing
parameters.
Path: Maintenance > Parameter Sync
(Optional) To modify the branch signal name of the power distribution unit, choose
System Settings > Signal Name Modify and access the Batch Signal Configuration to
modify the name, and then tap Submit.
The following is an example of how to display two branches for power distribution
unit1.
Choose Monitoring > Power Distribution > General Input Unit > Power
Distribution Unit > Display Configuration, select Branch Information Display
corresponding to QF1 and QF2, and then tap Submit.
Configure the power distribution settings for power distribution unit 1.
Parameter Name
QF1 Rated current (L1)
QF2 Rated current (L2)
NOTE
This parameter is not displayed for
some distribution units.
QF1 Branch circuit breaker in
use (L1)
QF2 Branch circuit breaker in
use (L2)
Upper load current threshold
Lower load current threshold
Set the parameters for other power distribution units in the same way or by
synchronizing parameters.
Path: Maintenance > Parameter Sync.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Default
Description
Value
32
Rated current 32 A for
each branch.
Enable
When the parameter is
set to Disable for a
branch, all alarms of the
branch will not be
reported.
When the parameter is
set to Enable for a
branch, all alarms of the
branch will be reported.
When the load current
80
exceeds the preset value,
an alarm is generated.
60
When the load current
exceeds the preset value,
an alarm is generated.
104