Access Management; Commissioning A Door Status Sensor; Commissioning A Door Status Sensor (Connected To The Ai/Di Port On The Independent Deployment Ai_Di Unit) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Step 8 (Optional) Click
connected to the COM ports of the UIM20A, and click
Step 9 (Optional) Click
Step 10 Choose Home > Plan View on the ECC800-Pro WebUI, and drag the dry contact device to
the corresponding position in the Smart Module View pane based on the actual device
layout.
----End

6.4 Access Management

6.4.1 Commissioning a Door Status Sensor

6.4.1.1 Commissioning a Door Status Sensor (Connected to the AI/DI port
on the Independent Deployment AI_DI Unit)
If a door status sensor is installed, perform the following steps to configure it.
Context
Procedure
Step 1 Set parameters for a door status sensor.
1.
2.
3.
4.
Issue 06 (2020-04-22)
, change the IT cabinet name, change the UIM and the devices
to delete a device binding relationship.
Hold down the BLINK button on the UIM for less than 2s. The RUN indicator on the UIM blinks fast,
and the cabinet corresponding to the UIM blinks in the smart module view.
To use the AI/DI sensor, enable the corresponding AI/DI port and name the sensor. After
that, the specific alarm can be reported.
If the sensor is prefabricated, only check its settings.
If multiple door status sensors are connected, commission one door status sensor first
and then commission the other door status sensors in the same way.
In this example, the door status sensor is connected to the AI/DI_1 port on the independent deployment
AI_DI 1.
Log in to the ECC800-Pro WebUI as an administrator.
Choose System Settings > Signal Name Modify. The Batch Signal Configuration
page is displayed.
Set Device Type to Independent Deployment AI_DI Unit, set Device Name to
Independent Deployment AI_DI1 Unit, and click OK.
On the query result tab page, set the new signal name of AI/DI_1 to Door1 and click
Submit.
Order number of door sensor name is same as cabinet.
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
in the Operation column.