Huawei ECC800 User Manual page 197

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual (for ECC800-Pro)
Parameter
Cabinet width
Power
Distrib
ution
Param
eter
Setting
s
rPDU-A01
rPDU-B01
Branch auto-fill
mode
Issue 06 (2020-04-22)
Setting
600
Power
Single-phase
system
Numb
2
er of
power
supplie
s
Rated
6.00
cabinet
power
PDU80001 > 1QF1(L1)
PDU80001 > 2QF1(L1)
Ascending order
Descending order
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
Description
The width of the cabinet.
Set single-phase or three-phase
based on the actual power supply.
rPDU quantity.
Set based on the actual rated
power of the cabinet.
Select a power distribution device
and power distribution branch for
the rPDU numbered rPDU-A01 in
the cabinet.
Select a power distribution device
and power distribution branch for
the rPDU numbered rPDU-B01 in
the cabinet.
Ascending order: If the branch
for the first cabinet is
1QF1(L1), 2QF1(L1), the
branches for subsequent
cabinets are 1QF2(L2),
2QF2(L2), and the like.
Descending order: If the
branch for the first cabinet is
1QF10(L1), 2QF10(L1), the
branches for subsequent
cabinets are 1QF9(L3),
2QF9(L3), and the like.