Group
11 START/STOP MODE
These parameters select the start and stop functions as well as the autophasing
mode, define the DC magnetising time of the motor, and configure the DC hold
function.
11
11 START/STOP MODE
Firmware block:
START/STOP MODE
(11)
11.01 START MODE
Selects the motor start function.
Notes:
• Selections
set to
• Starting to a rotating machine is not possible when DC magnetising is selected
CONST
• With permanent magnet motors, automatic start must be used.
• This parameter cannot be changed while the drive is running.
(0) FAST
(1) CONST TIME
(2) AUTOMATIC
[ Const time ]
[ 500 ms ]
[ Ramp ]
[ 5.0 rpm ]
[ 30 % ]
[ Disabled ]
[ Turning ]
FW block:
(0) FAST
and
(1) CONST TIME
(1)
SCALAR.
TIME).
DC magnetising should be selected if a high break-away torque is
required. The drive pre-magnetises the motor before the start. The
pre-magnetising time is determined automatically, being typically 200
ms to 2 s depending on the motor size.
Constant DC magnetising should be selected instead of DC
magnetising if constant pre-magnetising time is required (e.g. if the
motor start must be simultaneous with a mechanical brake release).
This selection also guarantees the highest possible break-away
torque when the pre-magnetising time is set long enough. The pre-
magnetising time is defined by parameter
ensure that the constant magnetising time is long enough to allow
generation of full magnetisation and torque.
Automatic start guarantees optimal motor start in most cases. It
includes the flying start function (starting to a rotating machine) and
the automatic restart function (stopped motor can be restarted
immediately without waiting the motor flux to die away). The drive
motor control program identifies the flux as well as the mechanical
state of the motor and starts the motor instantly under all conditions.
Note: If parameter
no flying start or automatic restart is possible by default.
START/STOP MODE
TLF10 2 msec
11.01 START MODE
11.02 DC MAGN TIME
11.03 STOP MODE
11.04 DC HOLD SPEED
11.05 DC HOLD CUR REF
11.06 DC HOLD
11.07 AUTOPHASING MODE
START/STOP MODE
(see above)
are ignored if parameter
WARNING! The drive will start after the set magnetising time
has passed even if motor magnetisation is not completed. In
applications where a full break-away torque is essential,
99.05 MOTOR CTRL MODE
22
(4)
99.05 MOTOR CTRL MODE
((0) FAST
11.02 DC MAGN
is set to
(1)
Parameters and firmware blocks
109
is
or
(1)
TIME.
SCALAR,