Switchgear Control Unit Sam600-Io Application Manual; Redundant Communication; Identification; Application - ABB Relion SAM600 Applications Manual

Switchgear control unit version 2.2
Hide thumbs Also See for Relion SAM600:
Table of Contents

Advertisement

Section 6
Ethernet-based communication
The default gateway can be selected by entering the IP address in
gateway is the router that is used to communicate with the devices in the other subnetwork.
By default this is set to
the entered value, but the default gateway has to be in the same subnetwork as the access
point. The default gateway is the router that is being used as default, that is when no route
has been set up for the destination. If communication with a device in another subnetwork is
needed, a route has to be set up. For more information on routes, see the
the
Technical manual and the Application manual .
6.2

Redundant communication

6.2.1

Identification

Function description
IEC 62439-3 Parallel redundancy
protocol
IEC 62439-3 High-availability
seamless redundancy
Access point diagnostic for
redundant Ethernet ports
6.2.2

Application

Dynamic access point diagnostic (RCHLCCH) is used to supervise and assure redundant
Ethernet communication over two channels. This will secure data transfer even though one
communication channel might not be available for some reason
Parallel Redundancy Protocol (PRP) and High-availability Seamless Redundancy (HSR) provides
redundant communication over station bus running the available communication protocols.
The redundant communication uses two Ethernet ports.
56
To increase security it is recommended to uncheck protocols that are not used
on the access point.
0.0.0.0 which means that no default gateway is selected. ECT validates
IEC 61850
identification
PRP
HSR
RCHLCCH
© Copyright 2017 ABB. All rights reserved
Default gateway . The default
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
-
-
-
-
GUID-172BA5D7-6532-4B0D-8C1D-2E02F70B4FCB v1
Switchgear control unit SAM600-IO
1MRK 511 445-UEN B
Routes chapter in
GUID-B7AE0374-0336-42B8-90AF-3AE1C79A4116 v1
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion sam600-io