156
Group
33 SUPERVISION
Configuration of signal supervision.
33
33 SUPERVISION
Firmware block:
SUPERVISION
(17)
Block outputs located in other
parameter groups
33.01 SUPERV1 FUNC
Selects the mode of supervision 1.
(0) DISABLED
(1) LOW
(2) HIGH
(3) ABS LOW
(4) ABS HIGH
33.02 SUPERV1 ACT
Selects the signal to be monitored by supervision 1. See parameter
Value pointer: Group and index
33.03 SUPERV1 LIM HI
Sets the upper limit for supervision 1. See parameter
Parameters and firmware blocks
SUPERVISION
TLF11 10 msec
[ Disabled ]
33.01 SUPERV1 FUNC
[ SPEED ACT ]
< 33.02 SUPERV1 ACT
(7 / 1.01)
[ 0.00 ]
33.03 SUPERV1 LIM HI
[ 0.00 ]
33.04 SUPERV1 LIM LO
[ Disabled ]
33.05 SUPERV2 FUNC
[ CURRENT ]
< 33.06 SUPERV2 ACT
(1 / 1.04)
[ 0.00 ]
33.07 SUPERV2 LIM HI
[ 0.00 ]
33.08 SUPERV2 LIM LO
[ Disabled ]
33.09 SUPERV3 FUNC
[ TORQUE ]
< 33.10 SUPERV3 ACT
(1 / 1.06)
[ 0.00 ]
33.11 SUPERV3 LIM HI
[ 0.00 ]
33.12 SUPERV3 LIM LO
6.14 SUPERV STATUS
(page 98)
FW block:
SUPERVISION
Supervision 1 not in use.
When the signal selected by parameter
below the value of parameter
SUPERV STATUS
is activated.
When the signal selected by parameter
exceeds the value of parameter
SUPERV STATUS
is activated.
When the absolute value of the signal selected by parameter
SUPERV1 ACT
falls below the value of parameter
LIM
LO, bit 0 of
6.14 SUPERV STATUS
When the absolute value of the signal selected by parameter
SUPERV1 ACT
exceeds the value of parameter
HI, bit 0 of
6.14 SUPERV STATUS
FW block:
SUPERVISION
FW block:
SUPERVISION
33.01 SUPERV1
45
(6)
6.14 SUPERV STATUS
(see above)
33.02 SUPERV1 ACT
33.04 SUPERV1 LIM
33.02 SUPERV1 ACT
33.03 SUPERV1 LIM
33.04 SUPERV1
is activated.
33.03 SUPERV1 LIM
is activated.
(see above)
33.01 SUPERV1
(see above)
FUNC.
falls
LO, bit 0 of
6.14
HI, bit 0 of
6.14
33.02
33.02
FUNC.