MODEL 7561-PSDS
PORTABLE SENSOR DISPLAY – STRAIN BRIDGE

Multi-Point

Multi point calibration allows linearization of up to 11 points. Note: the Points [+]
button must be used to add one point at a time. Once the input and output values
have been set the button will be enabled to allow another point to be added.
If the user knows what output is expected for known given input values, these can
simply be entered directly into the table for each point.
Alternatively, the user can apply input, click the Acquire button, and hit enter once the
values in the row are complete.
At a later date, the user can revisit this type of calibration and expand the number of
points to continue applying further calibration points. This is useful, for example, if
5 compression points are calibrated on one day then returned to complete 5 further
tension points on another day.
Points can be added in any order of input level.
Figure 47. Multi-Point Screen
Click into the field in the table on the right to set the Input and Output values.
TABLE 27. MULTI-POINT SCREEN
Item
No header
Input edit field
Acquire button
Output edit field
Description
This simply indicates which calibration point the row
refers to
If the input is known that gives a known output, then
click and enter the value here. Alternatively click the
Acquire button to automatically enter this value
Click to automatically apply the current input value. i.e.
apply 10 kg and enter 10 in the Output field then click
Acquire to automatically enter the current input value
Click and enter the required output value for the given
input value
Model 7561-PSDS User Manual |
Issue A
008-0752-00
sps.honeywell.com/ast
| 64