8.2.2 Output Circuit Mapping
Figure 8.3 is a simple example showing how to assign notification and relay output circuits to groups. For an example of a simple floor
above/floor below application, see Figure 8.5.
8.2.3 Event Mapping
There are 11 types of Zone events 14 types of Panel events, and 6 types of Site events that can be mapped (see Table 8.1). For each event
type, you can activate output groups and patterns. Mapping examples are shown in Figure 8.4, Figure 8.5 & Figure 8.6.
System
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
Figure 8.3 Example of Assigning Output Circuits to Groups
Zone
Manual Pull Alarm
Water Flow Alarm
Detector Alarm
(heat or smoke detectors)
Zone Aux 1 Alarm
Zone Aux 2 Alarm
Interlock Alert
Interlock Release
Pre-Alarm
Fire Supervisory
Status Point
CO Alarm
CO Supervisory
Table 8.1 : Event Types
Panel
System Aux 1 Alarm
System Aux 2 Alarm
Site
Fire Drill
General Fire Alarm
General Fire Supervisory
General Fire Pre-Alarm
LOC EVS 1-8 Alarm
General EVS Alarm
General EVS Supervisory
Point EVS 1-8 Alarm
99