Section 2: Agency Listings, Approvals, and Requirements

2.1 Federal Communications Commission (FCC)

1.
The following information must be provided to the telephone company before the 6820 or 6820EVS can be connected to the phone
lines:
This equipment complies with Part 68 of the FCC rules and the requirements adopted by ACTA. On the inside cover of this equipment is
a label that contains, among other information, a product identifier. If requested, this information must be provided to the telephone com-
pany.
A plug and jack used to connect this equipment to the premises wiring and telephone network must comply with the applicable FCC Part
68 rules and requirements adopted by the ACTA. A compliant telephone cord (not provided) and modular jack must be utilized with this
product. It is designed to be used with a modular jack that is also compliant.
The REN (ringer equivalence number) provided on this installation sheet is used to determine the number of devices that may be con-
nected to the public switched telephone network. This number must not exceed 5.0. Since this product has an REN of 1.0A, the number
of devices is limited. The REN number is embedded in the FCC registration number as 10A.
If the 6820 or 6820EVS causes harm to the telephone network, the telephone company will notify you in advance that the temporarily
discontinuance of service may be required. But if advance notice is not practical, the telephone company will notify the customer as soon
as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or procedures that could affect the operation of the
equipment. If this happens the telephone company will provide advance notice in order for you to make necessary modifications to main-
tain uninterrupted service.
If trouble is experienced with the 6820 or 6820EVS, for repair or warranty information, please contact Honeywell Silent Knight at 1-
800-328-0103 or www.silentknight.com. If the equipment is causing harm to the telephone network, the telephone company may request
that you disconnect the 6820 or 6820EVS until the problem has been resolved.
This product cannot be adjusted or repaired in the field. It must be returned to the factory for service.
This equipment is not designed for use with party line service. Connection to party line service is subject to state tariffs. You may contact
the state public utility commission, public service commission or corporation commission for information.
Since the 6820/6820EVS is a commercial fire alarm panel, it must be connected upstream of all other equipment utilizing the phone
lines. If you have questions about the installation, contact your telephone company or a qualified installer.
WARNING:
This Device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions: (1) This device
!
may not cause radio interference, and (2) This device must accept any interference received, including interference that may cause undesired
operation
CAUTION: To ensure proper operation, this equipment must be installed according to the enclosed installation instructions. To verify that
!
the equipment is operating properly and can successfully report an alarm, this equipment must be tested immediately after installation, and
periodically thereafter, according to the enclosed test instructions.
CAUTION: In order for "alarm dialing equipment" to be able to seize the phone line to report an alarm or other event when other customer
equipment (telephone, answering system, computer modem, etc.) connected to the same line is in use, "alarm dialing equipment" must be
connected to a properly installed RJ31X jack. The RJ31X jack must be connected in series with, and ahead of, all other equipment attached
to the same phone line. Series installation of an RJ31X jack is depicted in the figure below. If you have any questions concerning these
instructions, you should consult your telephone company or a qualified installer about installing the necessary jack and alarm dialing
equipment for you

2.2 Underwriters Laboratories (UL)

2.2.1 Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for
additional requirements. The following subsections list specific requirements for each type of installation (for example, Central Station
Fire Alarm systems, Local Protected Fire Alarm systems, and so on). See Section 10.7 for information on releasing operation.
1.
All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2.
Use the addressable smoke detectors specified in Section 7.2 (SD devices) or Section 7.1 (SK devices) of this manual and/or
conventional detectors listed in the compatibility chart. (See Appendix A).
12
A
Manufacturer:
B
Model Number:
C
FCC registration number:
Ringer equivalence:
D
Type of jack:
E
Facility Interface Codes:
F
Service Order Code:
Honeywell Silent Knight
6820 and 6820EVS
US: HS9AL10A2100
1.0A
RJ31X
Loop Start:
02LS2
9.0F
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 10/09/2017