Conditions Required for a Release Output Activation
Any release requires the activation of an interlock switch, and either a manual release switch or 2 activated addressable detectors. When
these conditions are met, the "Release" and "General Alarm" outputs will activate, and the "Pre-Alarm" output will deactivate.
Inputs
1st Addressable
Detector
2nd Addressable
Detector
Manual Release Station
Interlock/Pressure
Switch

10.8 Smoke Alarm Verification

Figure 10.10 illustrates how the Smoke Alarm Verification cycle operates.
During the Confirmation Period if there is no alarm indication then the system will return to normal operation.

10.9 Function Keys

The function keys (on the 6860 only) have multiple features. Their macro key functionality can simplify the disabling, activating, or
inhibiting points or groups respectively. They can also be used as a status type activation event and for activating Map Inhibit. Each F-
Key macro can hold 50 events.
To access the F-Key Recording menu:
1.
From the idle screen, press and hold the F-Key for 5 seconds.
2.
Enter a PIN with F-Key macro recording privileges, if prompted.
10.9.1 Recording an F-Key Macro
1.
Access the F-Key Recording menu and select the 'Start F-KEY Recording' option.
2.
The panel will return to the idle screen. Notice the 4th line on the display now alternates with <F# Key Recording>, where # is the
number of the F-Key being recorded.
148
x
x
x
x
x
x
x
Table 10.5 : Double Interlock Zone Operation
Figure 10.10 Smoke Verification Cycle
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
Output Results
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Silent knight 6820Silent knight 6820evs

Table of Contents