This test takes approximately 15 seconds to complete. You can press any key to end manually while the test is still in progress. When the
test ends, you will be returned to the <Test Menu>.
10.4.6 Conduct a Walk Test
Walk Test is a feature which allows one person to test the fire alarm system. The Walk Test will run for 4 hours or until the user manually
exits. If an alarm or pre-alarm condition is occurring in the system, you will not be able to enter the walk test. A walk test may only be
initiated if the test is enabled in the user profile.
1.
From the Main Menu, press 1 for System Tests.
If any alarm verification zones are being used, the user will be asked if they wish to disable alarm verification during
walk test. This occurs for either walk test option.
2.
Select 3 for Walk Test-No Rpt. Enter the time period you wish the NAC circuit to be active for each alarm (06 to 180 seconds). The
LCD will display "WALK TEST STOPPED" on Line 1 and "ENTER = start test" on Line 3. By selecting this option, central station
reporting is disabled while the test is in progress.
Select 4 for Walk Test-with Rpt. Enter the time period you wish the NAC circuit to be active for each alarm (06 to 180 sec-
onds). The LCD will display "WALK TEST STOPPED" on Line 1 and "ENTER = start test" on Line 3. By selecting this
option, central station reporting will occur as normal during the walk test.
The panel generates a TEST report to the central station when the walk test begins. During a walk test, the panel's normal fire
alarm function is completely disabled, placing the panel in a local trouble condition. All zones respond as 1-Count zones
(respond when a single detector is in alarm) during a walk test. Each alarm initiated during the walk test will be reported and
stored in the event history buffer.
3.
To End the Walk test, go to the main menu. Select 1 for System Test, then press 3 or 4. Press ENTER to end the walk test. The
system will reset. The panel will send a "TEST RESTORE" report to the central station.
If you do not end the walk test manually within four hours, it will end automatically. If an alarm or pre-alarm condition is occurring in
the system, you will not be able to enter the walk test.
NOTE: The panel does not do a full 30 second reset on resettable power outputs. As soon as the device is back to normal, the panel is ready
to go to the next device.
10.4.7 Conduct a Communicator Test
1.
From the Main Menu, press 1 for System Tests.
2.
Select 5 for Communicator Test. The screen will display "Manual Communicator Test started". When the test is completed, you
will be returned to the <Test Menu>.
3.
The Manual communicator test will be communicated out both Phone Lines and Ethernet/Cellular paths if they are all programmed.
Each manual communicator test will alternate between one of the Phone Line paths and one of the AlarmNet paths.
10.4.8 Manual AlarmNet Registration
1.
From the Main Menu, press 1 for System Tests.
2.
Select 8 for Register AlarmNet. The screen will display and ask for confirmation. Feedback will be given if the command was sent
or not.
10.4.9 Silence Alarms or Troubles
Press SILENCE and enter your code or rotate the key at the prompt. If an external silence switch has been installed, activating the switch
will silence alarms or troubles. If you are already using system menus when you press SILENCE, you will not need to enter your code or
rotate the key.
NOTE: Alarm and trouble signals that have been silenced but the detector remains un-restored will un-silence every 4 or 24 hours depending
on user selection (see Section , "Auto-Resound (4 or 24 hours)") until it is restored.
NOTE: Multi-Site displays do not allow for silencing multiple sites. Pressing SILENCE will only locally silence the PZT built into the
annunciator.
10.4.10 Reset Alarms
Press RESET and enter your code or rotate the key at the prompt. If an external reset switch has been installed, activating the switch will
reset alarms. If you are already using system menus when you press RESET, you will not need to enter your code or rotate the key.
NOTE: Multi-Site displays do not allow for resetting multiple sites.

Reset Communicator

This options allows the user to Reset the Communicator. The LCD will display:
"Resetting Communicator... Please Wait"
You will be returned to the Main Menu when the reset is complete.
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
IMPORTANT!
System Operation
117