Cisco Nexus 7009 Chassis Clearances

The Cisco Nexus 7009 chassis has different clearance requirements for installations with four-post racks or
cabinets, two-post racks with front-mount brackets, and two-post racks with center-mount brackets.
For four-post rack or cabinet installations, the chassis requires the following clearances (see
Clearances Required for a Front-Mounted Cisco Nexus 7009 Chassis in a Four-Post Rack, on page
• Front clearance requires both of the following:
Note
• Rear clearance includes both of the following:
• Side clearance of 11 inches (27.9 cm) for air flow on each side of the chassis.
Cable management frames
Vertical rack-mount posts
Vertical rack-mount posts for neighboring rack
Air intake from cold aisle for power supplies
Air intake from cold aisle for the supervisor and
I/O modules
Air exhaust to hot aisle for all modules and
power supplies
• Cabling area of 7.5 inches (19.1 cm) between the front of the chassis and the inside surface of the
cabinet or rack (this area can include the optional cable management frames)
• Maintenance area of 24 inches (61.1 cm) between the front of the rack or cabinet and the next object
in the cold aisle.
You might need to increase the maintenance area to accommodate a wide mechanical lift used to move the
chassis to or from the rack.
• Cabling area of 7 inches (17.8 cm) between the rear of the chassis and the inside surface of the
cabinet or rack
• Maintenance area of 24 inches (61.1 cm) between the rear of the rack or cabinet and the next object
in the hot aisle
9
Chassis width
10
Right side clearance recommended for open rack
installations:
• If next to another open rack, use 6 inches
• If next to a wall, use 11 inches (27.9 cm)
11
No rear clearance required but the rear must be
open to the hot aisle to exhaust air
12
Distance from front of vertical rack-mount posts
to rear of chassis
13
Clearance required between the front of the
chassis and the inside of the chassis for the cable
management frames and the optional front doors
14
Front service clearance required for installing
the chassis and replacing the modules
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
Cisco Nexus 7009 Chassis Clearances
(15.2 cm) between racks.
between chassis and wall.