Connecting The System Ground - Cisco Nexus 7000 Series Hardware Installation And Reference Manual

Hide thumbs Also See for Nexus 7000 Series:
Table of Contents

Advertisement

Installing a Cisco Nexus 7009 Chassis

Connecting the System Ground

After you have moved the chassis into the rack or cabinet, you are ready to connect the system to the data
center earth ground. After you ground the chassis, you can ground your ESD wrist strap by connecting it to
the chassis.
To connect the system ground to the data center earth ground, follow these steps:
SUMMARY STEPS
1. Use a wire-stripping tool to remove approximately 0.75 inch (19 mm) of the covering from the end of the
grounding wire.
2. Insert the stripped end of the grounding wire into the open end of the grounding lug as shown in
24: Inserting the Grounding Wire in the Grounding Lug, on page
3. Use the crimping tool to crimp the lug to the grounding wire. Verify that the ground wire is securely
attached to the ground lug by attempting to pull the wire out of the crimped lug.
4. Remove the adhesive label from one of the two system grounding pads, and secure the grounding wire
lug to the grounding pad with two M4 screws.
7009 Chassis, on page 56
that the grounding lug and the grounding wire do not interfere with other switch hardware or rack
equipment.
DETAILED STEPS
Step 1
Use a wire-stripping tool to remove approximately 0.75 inch (19 mm) of the covering from the end of the grounding
wire.
Step 2
Insert the stripped end of the grounding wire into the open end of the grounding lug as shown in
Grounding Wire in the Grounding Lug, on page
Figure 24: Inserting the Grounding Wire in the Grounding Lug
1
NRTL listed 45-degree grounding lug
Step 3
Use the crimping tool to crimp the lug to the grounding wire. Verify that the ground wire is securely attached to the
ground lug by attempting to pull the wire out of the crimped lug.
Step 4
Remove the adhesive label from one of the two system grounding pads, and secure the grounding wire lug to the grounding
pad with two M4 screws.
the location of the grounding pads on the front side of the chassis. Ensure that the grounding lug and the grounding wire
do not interfere with other switch hardware or rack equipment.
shows the location of the grounding pads on the front side of the chassis. Ensure
55.
2
Grounding cable with 0.75 in. (19 mm) of insulation stripped from the end
Figure 25: Grounding Pad on the Front of the Cisco Nexus 7009 Chassis, on page 56
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
55.
Figure 25: Grounding Pad on the Front of the Cisco Nexus
Connecting the System Ground
Figure
Figure 24: Inserting the
shows