Power Supply Configuration Modes
2 power supplies
3 power supplies
4 power supplies
12
Single input per power supply
220-V input
1 power supply
2 power supplies
3 power supplies
4 power supplies
12
The Cisco Nexus 7018 switch uses up to four 7.5-kW power supplies, the Cisco Nexus 7010 switch
uses up to three 7.5-kW power supplies, and the Cisco Nexus 7009 uses up to two 7.5-kW power
supplies.
Table 23: Power Availability for 3.0-kW DC Power Supplies
Power Inputs
Dual inputs per power
supply
13
1 power supply
2 power supplies
3 power supplies
4 power supplies
13
The Cisco Nexus 7004 uses up to four 3.0 kW DC power supplies.
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
160
Combined Mode
Power Supply
Redundancy Mode
15,000 W
7500 W
22,500 W
15,000 W
30,000 W
22,500 W
3750 W
—
7500 W
3750 W
11,250 W
7500 W
15,000 W
11,250 W
Combined Mode
Power Supply
Redundancy Mode
3,000 W
—
6,000 W
3,000 W
9,000 W
6,000 W
12,000 W
9,000 W
Technical Specifications
Input Source
Full Redundancy
Redundancy Mode
Mode
7500 W
7500 W
11,250 W
11,250 W
15,000 W
15,000 W
—
—
—
—
—
—
—
—
Input Source
Full Redundancy
Redundancy Mode
Mode
—
—
3,000 W
3,000 W
3,000 W
3,000 W
6,000 W
6,000 W