Telephone Requirements and Warnings

Battery Charger
CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the FACP. The FACP battery charger must be disabled, through
software programming, when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger
batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel.
Refer to the CHG-75 Manual for additional information.
CHG-120F Battery Charger
The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the FACP. The FACP battery charger must be disabled,
through software programming, when using the CHG-120F. The batteries and charger can be housed in the BB-55F battery box which
can be mounted up to 20 feet away from the control panel. Note that when using a BB-55F for housing the charger and batteries greater
than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for additional information.
PS-Tools Programming Utility
The PS-Tools Programming Utility can be used to locally or remotely program the FACP directly from most IBM compatible personal
computers (PC), running Windows
later to the control panel. The P/N: PK-CD includes the Windows-based Programming Utility software on CD-ROM with on-line help
file. A standard USB cable with male-A to male-B connectors, which must be purchased separately, is required for local connection of
the PC to the USB port J11 on the FACP main circuit board. Remote programming requires that the PC have a 2400 baud (or faster)
modem.
Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to "Remote
Download" on page 108). Remote interrogation of panel programming, history logs, detector status, etc., is possible without enabling the
remote download option.
1.7 Telephone Requirements and Warnings
1.7.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 0.0B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone
line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not
exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the
telephone company to determine the maximum REN for the calling area.
1.7.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble
is experienced with this equipment, for repair or warranty information, please contact:
Manufacturer:
Product Model Number: MS-5UD/MS-10UD
FCC Registration Number: 1W6AL00B10UD
Ringer Equivalence: 0.0B
Important! The DACT must not be used to dial a phone number that is call-forwarded.
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP
door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested,
this number must be provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this
even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dial-
ing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment
attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a quali-
fied installer about installing the RJ31X jack and alarm dialing equipment. Refer to "Digital Communicator" on page 30 for an illustra-
tion of the proper installation of this equipment.
1.7.3 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, ser-
vices, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give
advance notice of such changes or interruptions.
MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018
®
XP (or newer). FACP program files can also be created and stored on the PC and then downloaded
Fire•Lite Alarms
One Fire-Lite Place
Northford, CT 06472
(203) 484-7161
Product Description