System Options
Phone Line Gains
1.
Login to the panel. The panel will automatically access the main menu.
2.
Select 7 to access Panel Programming.
3.
Select 5 to access System Options.
4.
From the next menu, select 1 to access Communication Options.
5.
Select 5 to access Phone Line Gains.
6.
The available options are listed as follows:
• Dialing: Low, High (default), Normal
• Reporting: Low (default), High, Normal
8.6.2 Daytime/Nighttime Sensitivity
If you need to change the time that sensitivity levels take effect (that is, the time that "Day" and "Night" begin), follow these steps.
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 5 to access System Options.
4.
From the System Options menu, select 2 for Day/Night Sense.
A screen similar to the one shown below will display.
In this example, daytime sensitivity levels will be
observed between 6:00AM and 6:00PM Monday
through Friday. Night-time sensitivity levels will be
observed between 6:00PM and 6:00AM Monday
through Friday and all day on Saturday and Sunday.
8.6.3 Holiday Days
Up to 18 dates can be designated as holidays. When day/night sensitivity is enabled, all photoelectric smoke detectors in the system will use
night sensitivity for the entire day on days designated as holidays.
To add or change a holiday, follow these steps.
1.
Login to the panel.
2.
Select 7 to access the program menu.
3.
Select 5 to access System Options.
4.
Select 3 to select Holiday Days.
NOTE: For most installations, holiday programming will need to be performed each year to ensure correct dates.
5.
Select the holiday schedules you want to edit (1- holidays 1 - 9, 2- holidays 10 - 18).
6.
Enter the month of the holiday, then press ENTER.
7.
Enter the day of the month for the holiday, then press ENTER.
8.
Repeat steps 6 and 7 to add any remaining desired holidays.
8.6.4 Time Options
Use this programming option to set the following:
water flow delay time
IFP-75 Series Manual — P/N LS10147-001SK-E:E 4/6/2022
Dialing: High
Reporting: Low
<Dialing Gain>
Figure 8.11 Phone Line Gains
Enable Day/Night:NO_
Day Start: 06:00AM
Night Start: 06:00PM
Days of week:-MTWTF-
Figure 8.12 Changing Day/Night Sensitivity Time
Enter Holidays 1-9
01/01 07/04 12/24
12/25 --/-- --/--
--/-- --/-- --/--
Figure 8.13 Edit Holidays Screen
Enable day/night. If disabled, day
sensitivity is in effect at all times.
Day start time
Night start time
Sensitivity levels are
programmed in the zones menu.
pre-programmed holidays
programmable holiday locations
Programming