2: Time Options - Honeywell 6820 Manual

Addressable fire alarm conrol panel
Table of Contents

Advertisement

Programming
The selection made here must match the programming for this option in the Communication Configuration dialog box of HFSS.
13. Select Y (answering machine bypass enabled) or N (answering machine bypass disabled) by pressing the up or down arrow key, then
press ENTER.
Phone Line Unused
This option is used so that you can set unused phones lines to "Yes", so no auto-test will be sent through that line.
This option is factory programmed as No.
14. Select Y or N by pressing the up or down arrow key, then press ENTER.
Edit Ethernet
1.
Login to the panel. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Options.
5.
Select 3 for Edit Ethernet.
AlarmNet Timers
1.
Login to the panel. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Options.
5.
Select 4 for AlarmNet Timers.
6.
The available options for AlarmNet Timers are as follows: *default
• Ethernet: None, 75 seconds, 90 seconds, 3 minutes, *5 minutes, 1 hour, 24 hours, 30 days.
• Cellular: None, *24 hours, 30 days.
• Old Alarm: None, 10 minutes, 15 Minutes,*30 Minutes, 1 Hour, 2 Hours, 4 Hours, 6 Hours, 12 Hours, 24 Hours.
(Sets how long an undeliverable alarm is retried for delivery to the Central Station. If the message is not validated, it is retried until
the old alarm time is reached or the message is validated).
Phone Line Gains
1.
Login to the panel. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Options.
5.
Select 5 for Phone Line Gains
6.
The available options: *default
Dialing Gain:
– Low = 9 DB Attenuation
– Normal = 6 DB Attenuation
– *High = 3 DB Attenuation
Reporting Gain:
– *Low = 9 DB Attenuation
– Normal = 6 DB Attenuation
– High = 3 DB Attenuation
8.6.2 Time Options
Through this programming option you can set the water flow delay time, alarm verification time, AC report delay, AC-Frequency, Auto-
Resound, and Clock Format.
106
MAC:0000.0020.6894
MAC CRC:01E2
IP:158.100.049.148
<IP Address> More
Figure 8.9 Edit Ethernet Message
Ethernet: 5 Minutes_
Cellular: 24 Hours_
Old Alarm: 30 Minutes_
<Ethernet Supervise>
Figure 8.10 AlarmNet Timers
Sub:255.255.252.000
GW:158.100.048.254
DHCP:Y
<DHCP enable>
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
System Options