Buffer memory name
Recording status 1
7 CAMERA RECORDER MODULE (DETAILED SPECIFICATIONS)
272
7.4 Buffer Memory
*2
Data sampling
*1*2
Recording buffer storing status
Recording files saving completion
*1
Recording files saving error
Recording files saving completion code
Address
Un\G1506
Un\G1507
*1
Un\G1508
Un\G1509
*1
Un\G1510
Description
The sampling or accumulation status of devices and labels is
stored.
0: Not sampling
1: Sampling
■When selecting "File Saving Trigger Only" for the recording
method
• '1' (sampling) is stored when the recording function starts
running ('1' (operating) is stored in 'In recording operation'
(Un\G1501)) after starting the function.
• '0' (not sampling) is stored when saving a recording file
starts, and '1' (sampling) is stored after the file saving is
completed.
• '0' (not sampling) is stored when stopping the operation of
the recording function or a module stop error occurs.
■When selecting "Recording Startup Trigger + File Saving
Trigger" for the recording method
• '1' (sampling) is stored when a recording startup trigger is
satisfied, and '0' (not sampling) is stored after devices and
labels for a saving period are accumulated.
• When '1' (sampling) is stored, data accumulation stops and
'0' (not sampling) is stored if the capacity of accumulated
data exceeds that of the recording buffer. (Page 60
Recording buffer)
• '0' (not sampling) is stored when stopping the operation of
the recording function or a module stop error occurs.
Whether data in a sampled device and label is accumulated in
the recording buffer is stored.
0: No data
1: Data exists
'1' (data exists) is stored when a device and label are sampled
and data is accumulated in the recording buffer.
'0' (no data) is stored when saving a recording file starts.
When a recording startup trigger is satisfied, accumulated
data is discarded and '0' (no data) is stored.
When the operating status switches to 'operating' after starting
the recording function, '0' (no data) is stored. (It is initialized to
'0' (no data).)
The completion status of recording file saving is stored.
0: Not completed
1: Completed
The timing when a value is stored differs depending on the
recording operation setting of a camera recorder module
used. For details, refer to the following:
Page 277 Recording files saving completion (Un\G1508)
The status of an error when saving a recording file is stored.
0: No error
1: Error exists
The timing when a value is stored differs depending on the
recording operation setting of a camera recorder module
used. For details, refer to the following:
Page 277 Recording files saving error (Un\G1509)
The code of an error occurred when saving a recording file is
stored.
0: No error
Values other than 0: File saving failed (error code)
The timing when a value is stored differs depending on the
recording operation setting of a camera recorder module
used. For details, refer to the following:
Page 278 Recording files saving completion code