5.6

Recorder Module

This section explains the errors which may occur in a recorder module and the troubleshooting.

Checking methods

Checking method
System monitor of GX Works3
Buffer memory
Recording monitor
If multiple errors occur at the same time, take corrective action for the errors in chronological order.
Error code types
The status of an error that occurs in a recorder module can be determined with the statuses of the RUN LED and ERR LED.
RUN LED
ERR LED
OFF
ON, flashing
ON
Flashing
ON
ON
Error types
There are two types of errors of a recorder module as follows:
Error type
Category
Module stop error
Moderate error
Major error
Module continuation error
Minor error
Details
Error codes can be checked in the system monitor of GX Works3.
Page 158 Checking the module status
Error codes can be checked in the following buffer memory:
Page 218 Current error area (Un\G140 to 149)
Page 219 Error log area (Un\G150 to 311)
The operating status of the recording function for each recording setting can
be checked in the recording monitor.
Page 143 RECORDING MONITOR
Error status
Error code
Major error
3C00H to 3FFFH
Moderate error
2000H to 3BFFH
Minor error
1000H to 1FFFH
Module status
A module stops operating.
A module continues operating.
Description
An error such as a hardware or memory error that causes a
module to stop operating.
An error such as one in a setting or the firmware that causes
a module to stop operating.
An error such as a failure in saving a recording file that
causes a module to continue or stop operating.
Corrective action
Take corrective action for the error according to the error
code, and turn OFF the ERR LED by either of the
following operations:
• Turn the power OFF and ON.
• Reset the CPU module.
Take corrective action for the error according to the error
code, and turn OFF the ERR LED by any of the following
operations:
• Error clear request (Y3)
• Click the [Clear Error] button in the "Module
Diagnostics" screen.
• Turn the power OFF and ON.
• Reset the CPU module.