Mitsubishi Electric MELSEC iQ-R Series User Manual page 234

System recorder
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Project data saving specification area (Un\G14080 to 14199)
Whether to save project data to a save destination for a recording file can be specified for each recording setting.
Buffer memory name
Project data saving specification 1
Project data saving specification 2 to 4
■Project data saving specification 1 to 4 (Un\G14080 to 14083)
Use this to specify whether to save project data to a save destination for a recording file set in the recording setting for each
recording setting.
A value is cleared to the initial value (0) at either of the following timings:
• A CPU module is powered ON or reset.
• Saving project data is completed.
'ON' (1) is stored in the following case:
• "Save" is selected for "Automatic Saving at Recording Start" in the module parameter when the recording function starts
running.
Precautions
The operation is disabled while project data is being saved or prepared for saving.
Whether project data is being saved can be checked in 'Project data saving' (Un\G14000, Un\G14010, Un\G14020,
Un\G14030).
Co-recording status area (Un\G14200 to 14249)
The co-recording status can be checked.
A value in this area is cleared to the initial value (0) at the following timing:
• A CPU module is powered ON or reset.
Buffer memory name
Sent co-recording trigger total count
Sent co-recording trigger cancel count
Received co-recording trigger total count
Received co-recording trigger discard count
*1 When it reaches 65535 times, it returns to 1 and continues counting.
Co-recording setting information area (Un\G14250 to 14299)
The co-recording setting can be checked.
A value in this area is cleared to the initial value (0) at the following timing:
• A CPU module is powered ON or reset.
Buffer memory name
Co-recording setting
6 RECORDER MODULE (DETAILED SPECIFICATIONS)
232
6.4 Buffer Memory
Address
Description
Un\G14080
Use this to specify whether to save project data to a save destination for a
recording file specified in recording setting No.1.
• 0: OFF (not save)
• 1: ON (save)
Un\G14081 to 14083
Details are the same as project data saving specification 1.
Address
Description
Un\G14200
The number of sent co-recording triggers is stored. (Value to be stored: 0 to
*1
65535)
Un\G14201
The number of unsent co-recording triggers is stored. (Value to be stored: 0
*1
to 65535)
Un\G14202
The number of received co-recording triggers is stored. (Value to be stored: 0
*1
to 65535)
Un\G14203
The number of disabled co-recording triggers among those received is
stored. (Value to be stored: 0 to 65535)
Address
Description
Un\G14250
Whether to use co-recording is stored.
0: Not use
1: Use
*1

Advertisement

Table of Contents
loading

Table of Contents