Mitsubishi Electric MELSEC iQ-R Series User Manual page 232

System recorder
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Buffer memory name
Previous firmware update
information
Previous firmware update result
Project data saving status area (Un\G14000 to 14079)
The saving status of project data can be checked for each recording setting.
A value in this area is cleared to the initial value (0) at the following timing:
• A CPU module is powered ON or reset.
Buffer memory name
Project data saving
status 1
Project data saving status 2 to 4
■Project data saving
Whether project data is being saved to the save destination for a recording file set in the recording setting is stored.
Each value is stored at each timing as follows:
• Not saving (0): Saving project data is completed.
• Saving (1): Saving project data starts.
• Preparing for saving (2): Preparation for project data saving starts.
6 RECORDER MODULE (DETAILED SPECIFICATIONS)
230
6.4 Buffer Memory
History
Execution time (year)
information
Execution time (month)
Execution time (day)
Execution time (hour)
Execution time (minute)
Execution time (second)
Execution time (day of the
week)
Firmware version after
update
Firmware version before
update
Firmware update target
Firmware update result
Address
Project data saving
Un\G14000
Project data saving
Un\G14001
completion
Project data saving result
Un\G14002
Project data saving
Un\G14003 to 14004
completion code
Project data saving progress
Un\G14005
Un\G14010 to 14039
Address
Description
Un\G13413
The value of the year (four digits) when the firmware update
was executed is stored as a BIN code.
Un\G13414
The value of the month when the firmware update was
executed is stored as a BIN code.
Un\G13415
The value of the day when the firmware update was executed
is stored as a BIN code.
Un\G13416
The value of the hour when the firmware update was
executed is stored as a BIN code.
Un\G13417
The value of the minutes when the firmware update was
executed is stored as a BIN code.
Un\G13418
The value of the seconds when the firmware update was
executed is stored as a BIN code.
Un\G13419
The value of the day of the week when the firmware update
was executed is stored as a BIN code.
(0: Sun, 1: Mon, 2: Tue, 3: Wed, 4: Thu, 5: Fri, 6: Sat)
Un\G13420
The firmware version after update is stored.
(When the update is completed with an error, '0' is stored.)
Un\G13421
The firmware version before update is stored.
Un\G13422
The start input/output number of the module where the
firmware update was executed is stored.
Un\G13423
The execution result of the firmware update is stored.
• 1H: Normal end
• 100H: Flash ROM error
• 200H: Model mismatched
• 201H: File invalid
• 203H: Firmware update prohibited state
• 300H: Firmware data error
Description
The saving status of project data for recording setting No.1 is stored.
• 0: Not saving
• 1: Saving
• 2: Preparing for saving
Whether saving project data for recording setting No.1 is completed is
stored.
• 0: Not completed
• 1: Completed
The saving result of project data for recording setting No.1 is stored.
• 0: No failure
• 1: Failure
The saving completion code of project data for recording setting No.1 is
stored.
• 0: No failure
• Values other than 0: Failure (event code)
The progress rate (%) of project data saving to the save destination for
recording setting No.1 is stored.
It is initialized to '0' when starting project data saving.
(Value to be stored: 0 to 100%)
Details are the same as project data saving status 1.