Buffer memory name
Recording status 1
6 RECORDER MODULE (DETAILED SPECIFICATIONS)
222
6.4 Buffer Memory
Address
Recording buffer storing
Un\G1507
*1
status
Recording files saving
Un\G1508
*1
completion
*1
Recording files saving error
Un\G1509
Recording files saving
Un\G1510
*1
completion code
Recording files saving
Un\G1511
*1
count
Recording files saving
Un\G1514
*1
progress
Description
Whether data in a sampled device and label is accumulated in the recording
buffer is stored.
0: No data
1: Data exists
'1' (data exists) is stored when a device and label are sampled and data is
accumulated in the recording buffer.
'0' (no data) is stored when saving a recording file starts.
When a recording startup trigger is satisfied, accumulated data is discarded
and '0' (no data) is stored.
When the operating status switches to 'operating' after starting the recording
function, '0' (no data) is stored. (It is initialized to '0' (no data).)
The completion status of recording file saving is stored.
0: Not completed
1: Completed
The timing when a value is stored differs depending on the version of a
recorder module used. For details, refer to the following:
Page 225 Recording files saving completion (Un\G1508)
The status of an error when saving a recording file is stored.
0: No error
1: Error exists
The timing when a value is stored differs depending on the version of a
recorder module used. For details, refer to the following:
Page 225 Recording files saving error (Un\G1509)
The code of an error occurred when saving a recording file is stored.
0: No error
Values other than 0: File saving failed (error code)
The timing when a value is stored differs depending on the version of a
recorder module used. For details, refer to the following:
Page 225 Recording files saving completion code (Un\G1510)
The number of recording file saving executions (both successful and failed)
is stored.
It is initialized to '0' when the operating status switches to 'operating' after
turning the power ON or resetting a CPU module and starting the recording
function.
In addition, it is initialized to '0' when the operating status switches to
'operating' after adding or changing a recording setting and starting the
recording function.
When it reaches 65535 times, it returns to 1 and continues counting.
If it is reset, '0' is stored.
(Value to be stored: 0 to 65535)
The progress rate (%) of recording file saving is stored.
For a recorder module the version of which is 04 or later, the progress rate of
all recording settings including sub modules is stored.
It is initialized to '0' when the operating status switches to 'operating' after a
file saving trigger is satisfied or starting the recording function.
(Value to be stored: 0 to 100%)