Mitsubishi Electric MELSEC iQ-R Series User Manual page 196

System recorder
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error code
Error name
3026H
Recording Setting Error
3027H
Recording Setting Error
3028H
Recording Setting Error
3029H
Recording Setting Error
3030H to 3031H
Recording Setting Error
3032H
Recording Setting Error
3033H
Recording Setting Error
3034H
Recording Setting Error
3040H to 3044H
Control CPU Communication
Error
3045H
Control CPU Communication
Timeout
3050H to 3064H
Module Error
3070H to 3071H
Module Error
5 TROUBLESHOOTING
194
5.7 Camera Recorder Module
Error description
Device/label data which exceeds the size of
the buffer area for data sampling in the CPU
parameter is specified in the recording
setting file.
The program setting and FB/FUN file setting
in the CPU parameter in the CPU module
are different from the project (program
setting and FB/FUN file setting in the CPU
parameter) at recording setting.
• The program file and FB/FUN file in the
CPU module are different from the project
(program, FB/FUN) at recording setting.
• They are different from the program file
and FB/FUN file in the CPU module at
recording setting because the project
(program, FB/FUN) was changed during
recording operation.
The device/label operation is not set to
"Save" in the event history setting of the
CPU parameter.
A recording setting file which is not
supported by the firmware version of the
target camera recorder module was written.
• The mounting position and control CPU of
the camera recorder module are different
from the ones of the system parameter at
the recording setting.
• The mode of the module parameter is not
set to "Online" or the module status
setting of the system parameter (I/O
assignment setting) is set to "Empty" in
some Main.
A recording setting file which is not
supported by the firmware version of the
target camera recorder module was written.
The link-direct device, module access
device, or CPU buffer memory access
device specified for collection does not have
an access destination or is out of range.
Failed to communicate data with the control
CPU module.
The data communication with the control
CPU module has timed out.
Corrective action
Please read the CPU parameter and recording setting
file, and reduce the device/label data to be saving
targets so that the size is within the buffer area for data
sampling in the CPU parameter. Or, please increase the
size of the buffer area for data sampling in the CPU
parameter.
• Please write the CPU parameter and recording
setting file to the CPU module.
• Please read the CPU parameter and recording
setting file, and write them to the CPU module again.
• Please write the program file, FB/FUN file, and
recording setting file to the CPU module.
• When the program file and FB/FUN file in the CPU
module were changed during recording operation,
please write the recording setting file to the CPU
module again.
• Please read the program file, FB/FUN file, and
recording setting file, and write them to the CPU
module again.
Please set device/label operation to "Save" in the event
history setting of the CPU parameter.
Please check the version of the camera recorder
module, use a compatible product, and then write the
recording file again.
• Please check the mounting position and control CPU
of the camera recorder module.
• Please check the system parameter and actual
system configuration.
• Please review the recording operation setting of the
module parameter and set the number of modules of
"Main" to one.
• Please remove the module from Main where the
module status setting of the system parameter (I/O
assignment setting) is set to "Empty".
Please check the version of the camera recorder
module, use a compatible product, and then write the
recording file again.
• Please review the device/label sampling target
setting in the recording setting.
• If the Device/Label sampling target setting is set to
the Device/Label batch specification, review the
program used to set recording.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the camera recorder module.
Please consult your local Mitsubishi representative.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the camera recorder module.
Please consult your local Mitsubishi representative.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the camera recorder module.
Please consult your local Mitsubishi representative.
• Please take anti-noise measures.
• Please switch the CPU module to RUN after resetting
it. If the same error is displayed, a hardware error
may have occurred in the camera recorder module.
Please consult your local Mitsubishi representative.