Chapter 5 Troubleshooting; Recording Function - Mitsubishi Electric MELSEC iQ-R Series User Manual

System recorder
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

5
TROUBLESHOOTING
This chapter explains the errors which may occur in System Recorder and the troubleshooting.
5.1

Recording Function

This section shows the troubleshooting on the recording function.
Troubleshooting on starting the recording function
Symptom
Check point
Unable to start the recording
Is a recording setting for which the recording function starts
function.
written?
Is a CPU module in the RUN state?
Are programs and parameters when configuring a recording
setting written to a CPU module?
Are devices and labels that do not exist in the CPU parameter
and modules that are not mounted specified in the device/
label sampling setting in the recording setting?
(Page 118 Device/Label Sampling Setting)
Does the sampling size of a recording setting (total size of
devices and labels specified in the device/label sampling
setting) exceed the capacity of the buffer area for data
sampling in the CPU parameter?
(Page 118 Device/Label Sampling Setting, Page 94
Buffer area setting for data sampling)
Is the buffer capacity of a recording setting for which the
recording function starts set in the recording buffer setting in
the module parameter?
(Page 98 Recording buffer setting (recorder module),
Page 99 Recording buffer setting (camera recorder module))
Does a program run properly when the device/label batch
specification is enabled in the device/label sampling setting in
the recording setting? (Is a program accessing an unmounted
module running?)
(Page 118 Device/Label Sampling Setting)
Is a condition for a device, which is specified as a recording
startup trigger in a recording setting for which the recording
function starts, satisfied when selecting "Recording Startup
Trigger + File Saving Trigger" for "Recording Method" in the
saving period setting?
(Page 117 When selecting "Recording Startup Trigger +
File Saving Trigger" for "Recording Method", Page 25
Recording startup trigger)
Is a condition for a device, which is specified as a recording
startup trigger in a recording setting for which the recording
function starts, satisfied while the recording startup trigger is
enabled when selecting "Recording Startup Trigger + File
Saving Trigger" for "Recording Method" in the saving period
setting?
(Page 117 When selecting "Recording Startup Trigger +
File Saving Trigger" for "Recording Method", Page 25
Recording startup trigger)
Is a recorder module with a firmware version supporting the
function used in the following cases?
• Using a safety CPU
• Specifying a file server as the save destination for recording
files
(Page 307 Added and Changed Functions)
Corrective action
• Write a recording setting for which the recording function
starts.
• Switch the CPU module to the RUN state.
• Write the programs and parameters to the CPU module.
• Review the recording setting.
• Review the recording setting.
• Review the buffer area setting for data sampling in the CPU
parameter.
• Review the recording buffer setting in the module parameter.
• Check the mounted module.
• Review the program accessing an unmounted module.
• Satisfy the condition for the device.
• Satisfy the condition for the device.
■When using a safety CPU
• Update the module to a firmware version supporting a safety
CPU.
■When specifying a file server as the save destination for
recording files
• Change the save destination to an SD memory card.
• Update the module to a firmware version supporting saving
to a file server.
5 TROUBLESHOOTING