File Server Setting - Mitsubishi Electric MELSEC iQ-R Series User Manual

System recorder
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

File server setting

Window
Click the [Detail] button next to the cells of "Saving Destination" in the saving path setting.
Displayed items
Item
Storage Location
User Name
Password
[File Saving Test] button
*1 A save destination folder is not generated automatically. Create one in advance.
*2 Use '\' as a delimiter between directories.
*3 When using a multiple CPU system, do not specify the same folder.
*4 Specify it within 64 characters.
*5 To specify a host name, the DNS setting must be configured in the module parameter of a recorder module/camera recorder module.
Page 95 Module Parameters (Recorder Module/Camera Recorder Module)
*6 A file cannot be saved by specifying a user name that is joined to a domain. Specify one that is not joined to any domain.
*7 When configuring multiple modules, the test is also performed between a sub module and file server.
Page 67 Operation of the recording function when configuring multiple modules
3 RECORDING SETTING
138
3.5 Saving Path Setting
Description
Specify the folder path to a save destination in the following format (1 to 142 characters):
*4*5
• \\(host name
or IP address)\(folder path)
*6
Specify a user name
to access a file server (1 to 20 characters).
Specify a password to access a file server (1 to 127 characters).
Click this to perform the file saving test for a save destination.
When the test is successful, a file (0 bytes) with the following name is stored in the save destination folder.
• MELSEC_SMB_TEST_(setting number)(start I/O number of a recorder module/camera recorder module).txt
*1*2*3
*7