Recording status area (Un\G1500 to 3199)
The recording status can be checked.
Buffer memory name
Recording status 1
In recording operation
Recording start error
Recording start error cause
File saving trigger monitor
Recording files saving
Data sampling
Address
Description
Un\G1501
The operating status of the recording function is stored. (Page 63
Operating status)
0: Stopped
1: Operating
The timing when a value is stored differs depending on the version of a
recorder module used. For details, refer to the following:
Page 224 In recording operation (Un\G1501)
*1
Un\G1502
The status of an error when the recording function starts running is stored.
0: No error
1: Error exists
The timing when a value is stored differs depending on the version of a
recorder module used. For details, refer to the following:
Page 224 Recording start error (Un\G1502)
*1
Un\G1503
The code of an error that occurs when the recording function starts running is
stored.
0: No error
Values other than 0: Error code
The timing when a value is stored differs depending on the version of a
recorder module used. For details, refer to the following:
Page 224 Recording start error cause (Un\G1503)
Un\G1504
The status of a file saving trigger is stored.
0: Unsatisfied
1: Satisfied
When '1' (satisfied) is stored, recording startup triggers and file saving
triggers are disabled.
The period during which '1' (satisfied) is stored differs depending on the
version of a recorder module used. For details, refer to the following:
Page 225 File saving trigger monitor (Un\G1504)
Un\G1505
The saving status of a recording file is stored.
0: Not saving
1: Saving
The timing when a value is stored differs depending on the version of a
recorder module used. For details, refer to the following:
Page 225 Recording files saving (Un\G1505)
Un\G1506
The sampling or accumulation status of devices and labels is stored.
0: Not sampling
1: Sampling
■When selecting "File Saving Trigger Only" for the recording method
• '1' (sampling) is stored when the recording function starts running ('1'
• '0' (not sampling) is stored when saving a recording file starts, and '1'
• '0' (not sampling) is stored when stopping the operation of the recording
■When selecting "Recording Startup Trigger + File Saving Trigger" for the
recording method
• '1' (sampling) is stored when a recording startup trigger is satisfied, and '0'
• When '1' (sampling) is stored, data accumulation stops and '0' (not
• '0' (not sampling) is stored when stopping the operation of the recording
(operating) is stored in 'In recording operation' (Un\G1501)) after starting
the function.
(sampling) is stored after the file saving is completed.
function or a module stop error occurs.
(not sampling) is stored after devices and labels for a saving period are
accumulated.
sampling) is stored if the capacity of accumulated data exceeds that of the
recording buffer. (Page 60 Recording buffer)
function or a module stop error occurs.
6 RECORDER MODULE (DETAILED SPECIFICATIONS)
221
6.4 Buffer Memory