4.9.5 (Optional) Installing T/H Sensor Cables

Step 1 Install T/H sensors outside cabinets.
Issue 04 (2022-12-15)
NO TE
● T/H sensors should be installed 1.5 m (33 U) above the ground.
● Each smart cooling product supports a maximum of 10 T/H sensors outside cabinets.