ECC800 Data Center Controller
User Manual

7.8.2 Configuring PUE User-defined Mode

Context
This section describes how to configure PUE for the integrated PDC connected.
The functions of configuration buttons for the PUE user-defined mode are described as
follows.
Table 7-5 PUE configuration buttons
No.
1
2
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose System Settings > PUE Configuration.
Step 3 Ensure that PUE function is set to Enable.
Step 4 (Optional) If PUE function is set to Disable, select Enable from the drop-down list box and
click Submit.
Step 5 Set the PUE configuration mode to User-defined, and click Submit.
1.
Issue 06 (2020-01-02)
Figure 7-4 Performance data of the integrated UPS cabinet
b.
Calculate the PUE. PUE = Increment in the total active electricity energy of the
UPS input/Increment in the total active electricity energy of the IT load output =
27.7 kWh/16.4 kWh = 1.7.
Button
Description
Add
Adds new total power consumption or IT power consumption parameters.
Delete
Deletes a parameter setting for the total power consumption or IT power
consumption.
On the total power consumption configuration tab page, click Add to enter the total
power consumption configuration page. On the Select Device tab page, select
Copyright © Huawei Technologies Co., Ltd.