Huawei ECC800 User Manual page 144

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Parameters
Batt installation
time
Battery string
capacity
Current source
Battery string No.
Step 4 Set the wireless networking (802.15.4) function of CIMs and BIMs.
Before networking, ensure that all the CIMs and BIMs have no network parameters, that is,
the RF_Z indicator on the CIM is steady green and the RUN/ALM indicator on the BIM is
steady red.
1.
2.
3.
4.
Issue 06 (2020-01-02)
Description
Actual time at which batteries are
installed
Capacity of a single battery
Select a Hall effect sensor (0-xxx A).
The actual specifications of the Hall
effect sensor will apply.
Set this parameter based on the planned
codes for CIMs and battery strings.
If the RF_Z indicator on the CIM is not steady on (green), press and hold down the networking
switch on the CIM for 10–20 seconds to clear the original network.
If the RUN/ALM indicator on the BIM is not steady red, hold down the BIM networking switch for
at least 5 seconds to clear the original network.
Press the networking switch on the CIM for 2 seconds. The ALM indicator blinks red
once, and the RF_Z indicator turns from steady green to blinking green at super short
intervals, which indicates that the CIM is being networked.
Blinking at long intervals: The indicator is on for 1 second and then off for 1 second alternately.
Blinking at super short intervals: The indicator is on for 0.05 seconds and then off for 0.05 seconds
alternately.
Press the BIM networking switch for 2 seconds. When the RUN/ALM indicator turns
from steady red to blinking green at super short intervals, and finally to blinking green at
long intervals, the BIM connects to the CIM network.
It is recommended that BIMs be networked from the positive battery string terminal according to the
battery cable connection sequence.
Batteries are numbered depending on the sequence of connecting BIMs to the CIMs.
Perform networking operations on the next BIM only after networking for the previous
BIM is successful. Repeat
Press the CIM networking switch for 2 seconds. When the RF_Z indicator on the CIM
turns from blinking green at super short intervals to blinking green at long intervals, the
networking is complete.
Copyright © Huawei Technologies Co., Ltd.
Step 4.2
to add other BIMs to the CIM network.
5 Power-On Commissioning
Remarks
N/A
Set this parameter to a
value in the range of 0 to
1000 Ah. Obtain the
battery capacity from the
battery label or document.
N/A
Set this parameter to a
value in the range of 1 to
4.
135