Procedure
Step 1 Set the PDU8000 monitoring parameters.
1.
2.
3.
4.
Step 2 Add a PDU8000 (Modbus RTU).
1.
2.
Issue 06 (2020-01-02)
On the VNC screen displayed after the PDU8000 startup, tap System Info.
Choose System Information > Settings, enter the user name admin and password
000001, and press
If the PDU8000 uses Modbus TCP, set Communication to Automatic(DHCP) on the
displayed communication settings screen and the PDU8000 is discovered by ECC800
automatically and is connected to the ECC800.
The method of connecting the PDU8000 (Modbus TCP) to the ECC800 is the same as that for the
integrated PDU. Connecting the integrated PDU to the ECC800 by following the instructions in this
section.
If the PDU8000 uses Modbus RTU, tap Communication and set IP address assign to
Manual. And set Serial port baud rate to 9600, and Serial port address to 1 on the
displayed communication settings screen.
Figure 5-4 PDU8000 communication settings screen
Log in to the ECC800 WebUI as an administrator.
Add a PDU8000.
The setting example indicates that the PDU8000 is connected to the COM2 port on the
ECC800. If the PDU8000 is connected to another port, set the number of the connected
port.
Ensure that the baud rate of the PDU8000 is consistent with that of the COM2 port on the ECC800.
Ensure that the baud rate of the PDU8000 is consistent with that of the COM2 port on the ECC800.