ECC800 Data Center Controller
User Manual
3.
4.
Step 2 Add a PDU2000-M(C).
1.
2.
Table 5-8 Adding a PDU2000-M(C)
Path
Home > Device
Management
3.
Issue 06 (2020-01-02)
Figure 5-6 PDU2000-M(C) communications settings
Set the PDU2000-M(C) address to 1 (ranging from 1 to 41) by pressing DOWN and UP.
Press MENU to confirm the settings.
The parameter settings take effect only if you press MENU and then the PDU2000-M(C) buzzes and
restarts. If you do not press MENU, the PDU2000-M(C) buzzes and restarts automatically after 30s and
the setting parameters are not saved.
Log in to the ECC800 WebUI as an administrator.
Follow the instructions in the following table to add the PDU2000-M(C).
The setting example indicates that the PDU2000-M(C) is connected to the COM1 port
on the ECC800. If the PDU2000-M(C) is connected to another port, set the number of
the connected port.
Ensure that the baud rate of the PDU2000-M(C) (the default baud rate is 9600) is consistent with that of
the COM1 port on the ECC800.
Item
Device type
Connect to
Communications
port
Device address
Click Connect Test to check whether the PDU2000-M(C) connects to the ECC800
properly.
If the PDU2000-M(C) connects to the ECC800 properly, click Add Device.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select PDU2000-M(C) from the drop-down list
box.
Select ECC800 from the drop-down list box.
Select COM1 from the drop-down list box.
In this example, Device address is set to 1. During
actual configurations, set the device address for the
PDU2000-M(C) based on the actual situation.
5 Power-On Commissioning
103