Setting And Adding A Pdc Dc Meter - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
3.
----End

5.3.14 Setting and Adding a PDC DC Meter

Prerequisites
Procedure
Step 1 Set the communications address for the PDC DC meter.
1.
2.
3.
4.
Step 2 Add a PDC DC meter.
1.
2.
Table 5-11 Adding a PDC DC meter
Path
Home > Device
Management
Issue 06 (2020-01-02)
Click Connect Test to check whether the PMAC615 connects to the ECC800 properly.
If the PMAC615 connects to the ECC800 properly, click Add Device.
If the PMAC615 does not connect to the ECC800 properly, check whether the cable
between the PMAC615 and the ECC800 is connected properly, whether the
PMAC615 and ECC800 are running properly, and whether the input parameters are
consistent with the PMAC615 parameters.
The model of the PDC is PDU8000-0630DCV5-HVA002 and the BOM number is
02403121.
In this example, a straight-through cable is used to connect the PDC DC meter to the
COM2 port on the ECC800.
Tap Settings on the screen after the PDC DC meter is started.
Enter 1 in the displayed password dialog box, tap Enter, and then tap Confirm to enter
the setting screen.
Set the communications address. Tap the ID under Device ID on the displayed setting
screen, enter 2 (the actual value prevails) using the keyboard that pops up, and then tap
Enter.
Press the restart button at the rear of the HMI monitoring screen. Then the parameters
take effect.
The communications address is 1 by default, and the baud rate is 9600 by default.
Ensure that the baud rate of the DC meter is consistent with that of the COM2 port on the ECC800.
Log in to the ECC800 WebUI as an administrator.
Follow the instructions in the following table to add the PDC DC meter.
Item
Device type
Connect to
Communicatio
ns port
Device
Copyright © Huawei Technologies Co., Ltd.
Setting
Select DC Meter from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM2 from the drop-down list box.
In this example, Device address is set to 1. During
5 Power-On Commissioning
107