5.3.8 Setting and Adding a NetCol5000-A035 (over Modbus RTU)

Prerequisites
In this example, a straight-through cable is used to connect the NetCol5000-A035 to the COM
port on the ETH converter.
When connecting devices, you are advised to add devices one by one and ensure that the view
is consistent with the real object. If all devices have been added and powered on, only the
BLINK function of the ETH converter can be used to identify the mapping between the
NetCol5000-A035 and ETH converter.
Procedure
Step 1 Set the NetCol5000-A035 monitoring parameters.
1.
2.
Step 2 Add a NetCol5000-A035.
The NetCol5000-A035 connects to the smart ETH gateway through the ETH converter to
communicate with the ECC800.
After NetCol5000-A035 parameters are set, the ECC800 can automatically identify the access
of the smart cooling product.
Step 3 Set the running parameters and control parameters for the NetCol5000-C035 on the WebUI.
1.
2.
3.
4.
----End
Issue 06 (2020-01-02)
Enter the NetCol5000-A035 home page, click Settings, choose user name Admin and
enter password 000001. After login, the settings screen of the NetCol5000-A035 is
displayed.
Choose Settings > Comm Settings > Modbus Settings, and choose Baud rate to 9600
and set Comm address to 1–8.
The earlier version has Protocol setting on the screen. The actual screen prevails.
The NetCol5000-A035 can also be directly connected to a COM port of the ECC800.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > Air Conditioner > NetCol5000-C0351
0351 in NetCol5000-C0351 is variable and subject to change with the smart cooling product model and
connection sequence. 035 indicates the 35 kW model, and 1 indicates the smart cooling product
connection sequence. The displayed value prevails.
On the Running Parameters tab page, set smart cooling product running parameters,
temperature and humidity parameters, and alarm parameters.
On the Controls tab page, set the smart cooling product control parameters (such as
on/off control parameters).