ECC800 Data Center Controller
User Manual
Procedure
Step 1 Set the UPS5000-E monitoring parameters.
1.
2.
3.
Step 2 Add a UPS5000-E.
1.
2.
Table 5-3 Adding a UPS5000-E
Path
Home > Device
Management
Issue 06 (2020-01-02)
On the displayed screen after UPS5000-E startup, tap System Info.
Choose System Info > Settings, enter the user name admin and password 000001, and
press
.
Tap Communication and set RS485 baud rate to 9600, and RS485 address to 1 on the
displayed communication settings screen.
Ensure that the baud rate of the UPS5000-E is consistent with that of the COM port on the ETH
converter.
Figure 5-3 UPS5000-E communication settings
Log in to the ECC800 WebUI as an administrator.
Add the UPS5000-E.
Item
Device type
Connect to
Communications
port
Device address
Copyright © Huawei Technologies Co., Ltd.
Setting
Select UPS5000 from the drop-down list box.
Select ETH Converter n from the drop-down list
box.
Select COM1/COM2 from the drop-down list box.
In this example, Device address is set to 1. During
actual configurations, set the device address for the
UPS5000-E based on the actual situation.
5 Power-On Commissioning
94