Huawei ECC800 User Manual page 39

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Specifications
Table 3-19
Table 3-19 Technical specifications for a smart ETH gateway
Item
Power input
Power output
FE port
PoE port
BLINK
button
Indicators
Table 3-20
Table 3-20 Indicators on a smart ETH gateway
Indicator
PWR
RUN
Issue 06 (2020-01-02)
lists the environmental specifications for a smart ETH gateway.
Specifications
PWR_IN D-type power input terminal, for power cascading, input voltage
range: 45–55 V DC
PWR_OUT D-type power output terminal, for power cascading, output
voltage range: 45–55 V DC
48V_OUT1 and 48V_OUT2, terminal, output voltage range: 45–55 V
DC
Two FE ports, RJ45 terminal with an indicator, 10/100M communication
rate, for the cascading between smart ETH gateways and the
communication with the upper computer
Four PoE ports, RJ45 terminal with an indicator, 10/100M
communications rate, complying with IEEE802.3at
If you press the BLINK button once, the RUN indicator blinks
intermittently at super short intervals (blinking at super short intervals for
0.5s and then off for 0.5s) for 10s.
describes the indicators on a smart ETH gateway.
Color
Name
Green
Power input
status indicator
Green
Module
running status
indicator
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
Off
The power supply is
abnormal.
Blinking at
The smart ETH gateway
long
successfully registers with
intervals
the ECC800 and the software
runs properly (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at
The smart ETH gateway does
short
not register with the ECC800
intervals
(the indicator blinks at 4 Hz,
on for 0.125s and then off for
0.125s).
3 Device Description
30

Advertisement

Table of Contents
loading

Table of Contents