5.3.3 Setting and Adding a UPS5000-E

Prerequisites
In this example, a straight-through cable is used to connect the UPS5000-E to the COM port
on the ETH converter.
When connecting devices, you are advised to add devices one by one and ensure that the view
is consistent with the real object. If all devices have been added and powered on, only the
BLINK function of the ETH converter can be used to identify the mapping between the
UPS5000-E and ETH converter.
Issue 06 (2020-01-02)
Log in to the ECC800 WebUI as an administrator.
Choose Home > Device Management.
Figure 5-2 Page for adding a UPS2000-G
In this example, Communications port is set to COM2 that the UPS2000-G connects to on the
ECC800 and Device Address is set to 1. The actual settings prevail.
Ensure that the baud rate of UPS2000-G (the default baud rate is 9600) is consistent with that of the
COM2 port on the ECC800.
Click Connect Test to check whether the UPS2000-G connects to the ECC800 properly.
If the UPS2000-G connects to the ECC800 properly, click Add Device.
If the UPS2000-G does not connect to the ECC800 properly, check whether the
cable between the UPS2000-G and the ECC800 is connected properly, whether the
UPS2000-G and ECC800 are running properly, and whether the input parameters
are the consistent with the UPS2000-G parameters.
The section describes how to add a UPS2000-G in a single UPS scenario. In a parallel UPS scenario, if
the common communications address of the Modbus card is added to the ECC800, all UPS2000-Gs can
be connected to the ECC800.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
93