ECC800 Data Center Controller
User Manual
Check Method
Smoke dispersing method:
NOTICE
When testing the smoke detection function of the
multi-functional sensor, do not start the smart
cooling product or fan, because the air from the
smart cooling product or fan will interfere with the
smoke, and therefore affect the detection result.
Figure 5-15 Detecting smoke
(1) Smoke compartment
Step 3 (Optional) Set the audible and visual alarm linkage function for the multi-functional sensor as
required. For the operation details, see
----End
Issue 06 (2020-01-02)
multi-functional sensor.
Ignite a piece of paper and then put out the
open flame. Place the paper 5–10 cm away
from the smoke compartment, and let
smoke enter the smoke compartment
through the hole in the side of the
multi-functional sensor.
Send clean air to the smoke compartment
through the hole in the side of the
multi-functional sensor.