ECC800 Data Center Controller
User Manual
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Follow the instructions in the following table to add the WLDS600 water sensor.
Table 5-12 Adding the WLDS600 water sensor
Path
Home > Device
Management
Step 3 Click Connect Test to check whether the WLDS600 water sensor connects to the ECC800
properly.
----End
5.3.17 Setting and Adding an Independent Deployment AI/DI
Unit
Procedure
Step 1 Set monitoring parameters for the independent deployment AI/DI unit.
Set the independent deployment AI/DI unit address to 1 or 2 by setting the DIP switch on the
module.
The DIP switch consists of toggle switches 1-4 (from left to right). Toggle switches 1-3
specify the address of the independent deployment AI/DI unit. Toggle switch 4 specifies the
address of the RS485 build-out resistor. 0 indicates OFF, and 1 indicates ON.
Issue 06 (2020-01-02)
The default communications address 1 of the WLDS600 water sensor is used for connecting to the
ECC800, the default baud rate is 9600.
Ensure that the baud rate of the WLDS600 water sensor is consistent with that of the COM1 port on
the ECC800.
Item
Device type
Connect to
Communications
port
Device address
If the WLDS600 water sensor connects to the ECC800 properly, click Add Device.
If the WLDS600 water sensor does not connect to the ECC800 properly, check whether
the cable between the WLDS600 water sensor and the ECC800 is connected properly,
whether the WLDS600 water sensor and ECC800 are running properly, and whether the
input parameters are consistent with the WLDS600 water sensor parameters.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select Water Sensor from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM1 from the drop-down list box.
In this example, Device address is set to 1. During
actual configurations, set the device address for the
WLDS600 water sensor based on the actual
situation.
5 Power-On Commissioning