7.8.1 Configuring PUE Standard Mode

Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose System Settings > PUE Configuration.
Step 3 Set PUE function to Enable.
Issue 06 (2020-01-02)
Devices Connected
Integrated UPS cabinet
in the
FusionModule2000
Integrated PDU in the
FusionModule2000
Integrated UPS cabinet
and 48 V DC power
supply in the United
Arab Emirates project
48 V DC power supply
and AC power
distribution cabinet in
the
FusionModule1000A
Integrated UPS cabinet
in the
FusionModule1000A
The actual device
connected prevails.
When the configuration mode is set to Standard, the ECC800 can automatically calculate the PUE
of multiple devices connected in the N+1 and 2N scenarios.
When the configuration mode is set to User-defined, the devices whose total power consumption
can be customized include the AC meter, Integrated UPS cabinet, Integrated PDU, PDU8000 and 48
V DC power supply, and the devices whose IT power consumption can be customized include the
DC meter, Integrated UPS cabinet, Integrated PDU, PDU8000 and 48 V DC power supply.
Copyright © Huawei Technologies Co., Ltd.
PUE Calculation Method
PUE = Increment in the total active
electricity energy of the UPS
input/Increment in the total active electricity
energy of the IT load output
PUE = Increment in the total active
electricity energy of the PDU
input/Increment in the total active electricity
energy of the IT load output
PUE = Increment in (Total active electricity
energy of the UPS input + Total DC load
power of the 48 V DC power supply
multiplied by 95%)/Increment in (Active
electricity energy of the UPS output for IT
cabinets + Total DC load power of the 48 V
DC power supply)
PUE = Increment in the total active input
electricity energy of the AC power
distribution/Increment in the total DC
electricity energy of the IT load output
PUE = Increment in the total active
electricity energy of the UPS
input/Increment in the total active electricity
energy of the IT load output
PUE = (Increment in the total power
consumption of branches of the device
input*multiple)/(Increment in the total
power consumption of branches of the IT
load output*multiple)