How To Set And Add A Pdc Dc Meter - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
----End

5.3.17 How to Set and Add a PDC DC Meter?

Prerequisites
One end of the straight-through cable has been connected to the RS485 port on the PDC DC
meter, and the other end has been connected to the COM port on the ECC800.
Context
The model of the PDC is PDU8000-0630DCV5-HVA002 and the BOM number is 02403121.
Procedure
Step 1 Set the communications address for the PDC DC meter.
1.
2.
3.
4.
Step 2 Add a PDC DC meter.
1.
2.
Table 5-15 Adding a PDC DC meter
Path
Choose System
Settings >
Device
Management
and click Add
Device. The
parameters for
adding devices
are displayed.
Issue 07 (2020-03-16)
PMAC615 and ECC800 are running properly, and whether the input parameters are
consistent with the PMAC615 parameters.
Tap Settings on the screen after the PDC DC meter is started.
Enter 1 in the displayed password dialog box, tap Enter, and then tap Confirm to enter
the setting screen.
Set the communications address. Tap the ID under Device ID on the displayed setting
screen, enter 2 (the actual value prevails) using the keyboard that pops up, and then tap
Enter.
Press the restart button at the rear of the monitoring screen. Then the parameters take
effect.
The communications address is 1 by default.
Log in to the ECC800 WebUI as an administrator.
Add a PDC DC meter.
Parameter
Name
Device
attribute
Device Type
Connect To
Communicatio
ns Port
Copyright © Huawei Technologies Co., Ltd.
Setting
Select Electricity Meter from the drop-down list
box.
Select LF DC Meter from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM2 from the drop-down list box.
NOTE
The setting example indicates that the DC meter is
connected to the COM2 port on the ECC800. If the DC
meter is connected to another port, enter the number of the
5 Power-On Commissioning
108